Type a branch, a subject or a topic — “round robin”, “paging”, “civil”.

Protection and Discrimination

Two requirements that fight each other: be fast, and trip nothing unnecessary. Every scheme in the topic is a different resolution of that conflict.

Skip to the animation

Protection must clear a fault fast enough to limit damage and preserve stability, and disconnect only the faulted element — two requirements that conflict, and every scheme in the topic is a different resolution of that conflict.

The central conflict

Speed limits I²t damage and keeps the system stable. Selectivity normally means waiting to see whether a downstream device acts first — which is exactly what speed forbids.

The two design virtues are stated as dependability (never fail to operate) and security (never operate when you should not). They also trade against each other, and different applications weight them differently.

Grading by time and by current

Time grading gives each upstream device a longer delay. It is simple and completely reliable, and it puts the longest delay at the source end where fault current is largest — correct discrimination achieved in the worst possible way.

IDMT relays operate faster the larger the current, so a close-up fault is also cleared sooner. Two settings — pick-up current and a time multiplier that shifts the whole curve — give discrimination without punishing severe faults with long delays.

Distance protection

A relay measuring V/I sees an impedance proportional to the distance to the fault, so it grades by position rather than by waiting.

ZoneReachDelayPurpose
Zone 180% of the lineInstantaneousPrimary, fast
Zone 2120% of the line≈ 0.4 sCovers the last 20% and backs up the next line
Zone 3Further still≈ 1.0 sRemote backup

Zone 1 stops at 80% because measurement error must never let it overreach into the next line. The remaining 20% is cleared by the far end's zone 1, or instantaneously by both if a communication channel is available.

Differential protection

Compare the current entering a zone with the current leaving it. Equal means healthy; a difference means current is escaping inside the zone. It is instantaneous and perfectly selective — a fault outside the zone produces no difference at all — which resolves the central conflict completely for the zone it covers.

  • Ideal for transformers, generators and busbars, where both current transformers are metres apart.
  • For a transmission line it needs a communication channel; fibre has made line differential routine.
  • CT saturation during heavy external faults creates a false difference, handled with a percentage-bias characteristic.
  • Transformer differential must also block on magnetising inrush, which looks like an internal fault and is not.

Backup

Relays, breakers and trip supplies all fail, so every scheme has a backup sharing as little as possible with the primary — different manufacturer, separate battery, separate CT core.

Breaker-fail protection is the last line: if current still flows after a trip command, it opens every breaker around the stuck one, deliberately disconnecting healthy circuits. A stuck breaker is rare and its consequence unbounded, which justifies a dedicated scheme.

Auto-reclose

Roughly 80% of overhead faults are transient — a bird, a branch, a lightning flashover — and clear once the current stops. Auto-reclose waits a dead time long enough for the arc to deionise and short enough to preserve stability, typically 0.3 to 1 second, then recloses.

On a permanent fault it trips again and locks out. It is never used on underground cable, where every fault is permanent and reclosing simply causes a second, larger failure.

The numbers you will be asked for

IDMT standard inverse

t = TMS × 0.14 / ((I/I_s)^0.02 − 1)

Distance measurement

Z_seen = V_relay / I_relay ∝ distance

Differential

I_diff = |I_in − I_out| · trips if > bias setting

Percentage bias

I_diff > k · I_bias + I_setting

Grading margin

typically 0.3 – 0.4 s between successive devices

Watch it work

loading visualisation…

Check yourself

question 1 / 4

One question at a time. Pick an answer to see why it is right or wrong, then move on — there is no score to keep and nothing is saved.

Why do protection's two requirements conflict?
What is wrong with pure time grading?
Why does a distance relay's zone 1 reach only 80% of the line?
Why is auto-reclose never used on underground cable?

0 / 4

4 still unanswered — the dots above jump straight to them.